PRELIMINARY:
- TURN OFF AC BREAKER
- DISCONNECT LOAD
- TURN ON AC BREAKER
|
|
TOOLS:
- SCREWDRIVERS
- DIGITAL MULTIMETER
- PROPER LOAD
|
| |
POSSIBLE CAUSES |
DOES THE BREAKER TRIP
(FUSE BLOW) IMMEDIATELY?
|
 |
- IMPROPER AC LINE VOLTAGE
- SHORTED RECTIFIER SCR
- FAULTY AC BREAKER
- SHORTED TRANSFORMER WINDING
- SHORTED SURGE SUPPRESSOR
|
 |
|
|
IS AC POWER LED LIT?
|
 |
- FAULTY LED CIRCUIT
- FAULTY LED
|
 |
|
|
IS THERE OUTPUT VOLTAGE?
|
 |
- LOSS OF AC POWER
- TRIPPED BREAKER OR BLOWN FUSE
- FAULTY CONTROL CARD
- LOOSE CONNECTION
- FAULTY VOLTMETER
- OPEN TRANSFORMER WINDING
- OPEN CHOKE
- BOTH SCRs OPEN
|
 |
|
IS THE OUTPUT VOLTAGE
THE CORRECT VALUE?
|
 |
- INCORRECT FLOAT OR EQUALIZE SETTINGS
- ONE SCR OPEN
- LOOSE CONNECTION FROM (+) OUTPUT TO PIN 12 ON CONTROL CARD
- FAULTY CONTROL CARD
- INCORRECT VOLTAGE PROGRAM RESISTOR
- FAULTY TRANSFORMER
|
 |
|
IS THE OUTPUT RIPPLE
WITHIN LIMITS?
|
 |
- SHORTED CHOKE
- FAULTY CAPACITOR
- IMPROPER FILTER CIRCUIT
|
 |
|
IS VOLTAGE REGULATION
WITHIN LIMITS?
|
 |
- FAULTY CONTROL TRANSFORMER
- FAULTY CONTROL CARD
- LOOSE CONNECTION FROM POWER XFRMR
TAPS 15 AND 16 THRU CONTROL XFMR
TO CONTROL CARD
|
 |
|
- TURN OFF AC BREAKER
- CONNECT LOAD
- TURN ON AC BREAKER
|
|
IS OUTPUT VOLTAGE
STILL CORRECT?
|
 |
|
 |
|
IS OUTPUT CURRENT
CORRECT?
|
 |
- UNIT IN CURRENT LIMIT
- IMPROPER LOAD
- FAULTY CONTROL CARD
- LOOSE WIRE CONNECTIONS
FROM SHUNT TO CARD
|
 |
|
|
DOES CURRENT LIMIT?
|
 |
- IMPROPER LOAD
- FAULTY CONTROL CARD
- LOOSE WIRE CONNECTIONS
FROM SHUNT TO CARD
|
| UNIT WORKS PROPERLY! |
|